7.6 Mains Power Connections
7.7 Relay Output Board Connections
Fig. 7.10 AC Power Supply
Warning.
Use fuse rating – 400 mA (max.) type T.
Fig. 7.11 DC Power Supply
Warning.
Use fuse rating – 3 A (max.) type T.
Terminal Block J
L
N
100 to 240 V AC
±
10 %
(90 min. to 264 V max.)
50/60 Hz
1
2
3
4
5
6
7
8
Line
Neutral
Fuse,
400mA, Type T
24V DC
Fuse,
3A, Type T
Terminal Block J
1
2
3
4
5
6
7
8
+
-
Note.
The maximum total combined current flowing through
the relays is 36 A. The maximum individual relay
current is 5 A.
The polarity is selected during I/O module
configuration – see Section 6.7.2, page 102.
Fig. 7.12 Relay Connections
Note.
Relay contacts are fitted with arc suppression
components as standard.