Configuration Signal type
Reset
Timer delay
Time
P.01
Equivalent
contacts
2 x NO, 24 VDC
or signal from
T1/T2
Manual reset
Off-delay
0.0 s, 0.5 s, 1.0
s, 1.5 s, 2.0 s,
3.0 s, 5.0 s,
10.0 s, 15.0 s,
30.0 s
P.02
Automatic
reset
P.03
Antivalent
contacts
NO + NC, 24
VDC or signal
from T1/T2
Manual reset
P.04
Automatic
reset
P.05
Pressure
sensitive
device
Square wave
from T1/T2
Manual reset
P.06
Automatic
reset
P.07
Two-hand
device
8.9
Configuration in preset mode
- - -
Sto
t. 0
P.01
1b
2b
3a
5
1a
4a
2a
1
2
4
3
3b
1.
Preset mode.
a. Push the Increment button to select type of preset configuration or to select custom
mode [CUS].
b. Push the Select button to step to the Timer setting.
2. Timer setting.
a. Push the Increment button to step between the available time settings.
b. Push the Select button to confirm the setting and step to store mode [Sto].
3. Store mode.
a. Push and hold the Select button to store the configuration.
b. Push the Select button to return to Preset mode.
4. Failsafe mode waiting for power cycling.
a. Power cycle (power off and on) the safety relay.
5. The safety relay is in operation mode with a preset configuration.