Configuration with TTH300 transmitters
12 SensyTemp
TSP
SM/TSP/SIL-EN
9 Configuration with TTH300 transmitters
The device was configured and tested according to customer order.
The device can be additionally configured with the local HMI or DTM using the HART interface.
Other configuration tools such as mobile handheld terminals are not described in these
instructions.
During setup, proper operation of the device is not ensured.
Warning!
Inspections:
Before commissioning the device, check as part of the safety function whether the device
setup supports the safety function for the system.
Make sure that the proper device was installed at the correct measuring point.
Each time the device is updated as part of the safety function, e.g., changing the mounting
position for the device or modifying the setup, the safety function of the device must be
checked again.
After checking the safety function, the device must be write-protected to prevent unintended
changes to the setup, since every change to the measurement system or parameters could
affect the safety function.
To ensure safe operation, the device must be write-protected.
To do so, follow these steps:
Activate/deactivate write protection
1. Write protection using local HMI (human-machine interface).
Go to “Device Setup", “Write Protection” and then enter the password “0110” to activate write
protection and password "0110" to disable write protection. (see operating instructions)
2. Write protection via DTM
Go to “Device Setup” and select “Write Protection” to activate the function.
If the device is locked (write-protected), it cannot be configured. Write protection is applied
for the entire device. Enter the password “0110” to disable write protection.
Summary of Contents for SensyTemp TSA101
Page 16: ...Safety engineering parameters 16 SensyTemp TSP SM TSP SIL EN ...
Page 18: ...Management Summary FMEDA 18 SensyTemp TSP SM TSP SIL EN 12 Management Summary FMEDA ...
Page 19: ...Management Summary FMEDA SM TSP SIL EN SensyTemp TSP 19 ...
Page 20: ...Management Summary FMEDA 20 SensyTemp TSP SM TSP SIL EN ...
Page 21: ...Management Summary FMEDA SM TSP SIL EN SensyTemp TSP 21 ...