background image

CSS sahara_02_04_instructions.doc

,    

Page 

6

 of 

12

All  units  have taps located in the High Voltage winding. The tap arrangement is shown on the nameplate
of  the  transformer. These taps are provided to furnish rated output voltage when the input voltage differs
from the rated voltage.

To change tap connections, do the following steps:

1. De-energized the unit, short-circuit both the  high  and low voltage connections and ground both

sides.

2. Unlock the tap changer handle, and then move the  taps changer handle to the desired tap, then

locked the tap changer handle.

3. Remove safety shorts and ground connections from the high voltage and low voltage buses.

After  ensuring that no tools or hardware was left in the enclosure, and the enclosures are closed properly,
you  may then re-energize the Package Compact Substation. Make sure that the tap connections are proper
for the required voltage as listed on the nameplate.  The transformer is normally shipped with the tap
changer for the rated voltage.

Cable Connections

When making outside cable connections, conductors suitable for at least 85°C should be used. All
connections should be made without placing undue stress on the terminals.

Conductors  should be securely fastened in place and adequately supported with allowances for expansion
and contraction.

FINAL INSPECTION PRIOR TO ENERGIZATION

After the Package Compact Substation has been found to be in good condition and the protective
equipment is operational, the substation may be connected to the network. However, it is recommended
that  the transformer to be left to settle for 1 or 2 days after installation so those air bubbles in the oil have
time to dissolve before connecting the voltage.

Before energizing the unit, a complete electrical  inspection  should  be made. The following checklist
should be used as a minimum requirement.

Electrical Inspection

[  ]

All external connections have been made properly (phasing of connections to terminals, etc.).

[  ]

All connections are tight and secure.

[  ]

All accessory circuits are operational. Check the  transformer  protective  equipment and test the
function of their electrical circuits:

Thermometers (alarms, tripping)

Pressure relay (tripping)

Oil level indicator

Ensure that all fuses are inserted and in the correct position

[  ]

All tap connections are properly positioned.

[  ]

The neutral and ground connections have been properly made.

Mechanical Inspection

WARNING  WARNING  WARNING  WARNING  WARNING  WARNING

TAP CONNECTIONS MAY BE CHANGED ONLY WHEN THE UNIT IS

 TOTALLY DE-ENERGIZED.

Summary of Contents for SAHARA Series

Page 1: ...pment ABB Electrical Industries Co Ltd Kingdom of Saudi Arabia ABB SAHARA Series Compact Substation OPERATING INSTRUCTIONS MODELS 24kV 36kV SAHARA 500 SAHARA MAX 1 SAHARA 1000 SAHARA MAX 2 SAHARA 1600...

Page 2: ...al Inspection 7 MAINTENANCE AND PERIODIC INSPECTION 7 Bolt Tightness 7 Inspection and Testing 7 Routine Field Testing 8 1 Insulation Resistance Test 8 2 Connection Test 9 3 Mechanical Operation 9 TRAN...

Page 3: ...tance of care in Site selection and design embodying features that provide adequate ventilation protection and security and which have taken account of appropriate fire moisture and explosion hazards...

Page 4: ...on has not sustained any damage during transportation Immediately upon receipt of the Package Compact Substation examine them to determine if any damage or loss was sustained during transit If abuse o...

Page 5: ...LIFT OR MOVE A TRANSFORMER OR PACKAGE COMPACT SUBSTATION WITHOUT ADEQUATE EQUIPMENT AND PRECAUTIONS 2 TERMINALS ARE FOR ELECTRICAL LOADING ONLY 3 DO NOT MAKE ANY CONNECTIONS THAT ARE NOT AUTHORIZED BY...

Page 6: ...ue stress on the terminals Conductors should be securely fastened in place and adequately supported with allowances for expansion and contraction FINAL INSPECTION PRIOR TO ENERGIZATION After the Packa...

Page 7: ...wings and previous test records before starting activity Scrutinize maintenance instructions given for the equipment to be maintained Maintenance information is given in the Operation and Maintenance...

Page 8: ...stigated for possible contamination on the surfaces NOTE For individual circuit protective device s resistance readings load and line conductors should be disconnected If not disconnected the test mea...

Page 9: ...tenance measures can be carried out which can not normally be performed during operation Before starting maintenance work the transformer has to be disconnected from the network and earthed or grounde...

Page 10: ...en of milliamperes With the same voltage reading the current taken by other phases can be measured The excitation currents of different phases should be approximately the same magnitude In a damage ph...

Page 11: ...nergy may be different for different fuse types as well as the selection tables and protection characteristics It is compulsory to use the same type of fuse links in all phases type rated current The...

Page 12: ...ring periodic checks established the best fixed periods for maintenance work It is also advisable to refer to the following rules The circuit breakers that operate rarely or which remain closed or ope...

Reviews: