![ABB SafePlus XT Installation And Operating Instructions Manual Download Page 24](http://html.mh-extra.com/html/abb/safeplus-xt/safeplus-xt_installation-and-operating-instructions-manual_2838053024.webp)
24
SAFERING XT/SAFEPLUS XT
Before using Defeat Interlock.
1. Ensure the Switch-Disconnector/Disconnector of
respective module is in Earth position
2. Ensure cable door is opened condition
3. Engage the defat Interlock
with Interlock Pin
B
4. Follow the arrow
i) Engage defeat interlock with Pin.
ii) Pull down the Defeat interlock (10-12mm).
iii) Engage the defeat interlock with flange.
To remove Defeat Interlock follow the arrow in reverse
direction.
Ensure the Switch-Disconnector/Disconnector of respective
module is in Earth position.
iii) Dis-engage the defeat interlock from flange
C
ii) Lift the Defeat interlock (10-12mm)
i) Pullout defeat interlock from Pin
i
Once all the work is done refix the cable door
(For more details refer chapter 8.1.1 & 8.1.2)
DANGER !
Defeat interlock will allow the operation from Earth to Off
Or Off to Earth operation only when defeat interlock is
inserted fully.
Do not try or operate disconnector/switch disconnector
forcefully to ON position, by using Defeat Interlock.
—
Figure 8.6
Defeat step 1 to step 4
B
i
C
ii
A
iii