33
Fig. 32. Parameter selection key for annunciator unut SACO 16D1.
Parameter
selection key
Channel
input delay
Channel
reset delay
Contact
type
Channel
indication
0 = 5 ms
1 = 20 ms
2 = 100 ms
3 = 1 s
4 = 5 s
5 = 20 s
6 = 60 s
7 = 160 s
0 = 5 ms
1 = 20 ms
2 = 100 ms
3 = 1 s
4 = 5 s
5 = 20 s
6 = 60 s
7 = 160 s
0= NO contact
1= NC contact
2= NO contact,
no return
3= NC contact,
no return
4= NO and NC
contact
Pulse counters:
5= NO contact
6= NC contact
7= NO and NC
contact
0= seq. 0-4
1= seq. 0-4
audible also
at return to
normal
2= field cont.
following,
no flashing,
or audible
DISPLAY
PARAMETER
Input
Channel reflash A
Channel reflash B
- - = no group alarm
01= group alarm 1
-
-
-
16= group alarm 16
- - = no group alarm
01= group alarm 1
-
-
-
16= group alarm 16
Interlocking function 1
Interlocking function 2
Type of
interlocking
Interlocking
group
Type of
interlocking
Interlocking
group
0= interlocking
output
1= channel
reflash A
interlocked
2= channel
interlocked
3= channel
interlocked
- = not grouped
1= group 1
2= group 2
3= group 3
4= group 4
5= group 5
6= group 6
7= group 7
8= group 8
0= interlocking
output
1= channel
reflash A
interlocked
2= channel
interlocked
3= channel
interlocked
- = not grouped
1= group 1
2= group 2
3= group 3
4= group 4
5= group 5
6= group 6
7= group 7
8= group 8
Group alarm number
Type of reflash relay function
01= group alarm relay 1
02= group alarm relay 2
-
-
-
16= group alarm relay 16
0= field contact
following
1= alarm memory
following
2= 300 ms pulse
3= 0 + 2
Unit identification number
Sequence
Serial comm.
01= number 1
02= number 2
-
-
-
99= number 99
0= ISA A
1= ISA A-1
2= ISA M-1
3= ISA R-1
4= DIN 19235
0= syncr. input
1= syncr. output
2= 9600 Bd
3= 4800 Bd
4= 2400 Bd
5= 1200 Bd
6= 300 Bd
Group
Interlock
Output
Module
Parameter selector
Display cursor
Channel selector
M
Data value selector
Store (Reset)
Channel
input settings
Channel-related anti-pumping
00= supervision disabled
00…99= allowed number of
registrations per minute
Reflash
grouping
Configuration
of interlockings
Group alarm
settings
Annunciator
module settings