Further explanations on the use of the "SD-TU Interface" software can be found in the software's
own on-line help. 

5.2.1

SW updating procedure

1. Switch on the SACE PR010/T test unit.
2. Connect the SACE PR010/T test unit (connector 3) to one of the PC's serial ports (COM1...

COM4) using the cable supplied. 

3. Run the "SD-TU Interface.exe" program.
4. From the list of devices that appears in the "Device selection" window on the left of the

screen, use the mouse (holding down the left key) to select the device you want, dragging it
into the "Device" window that appears on the right.

5. Repeat the selection operation indicated in point 4 for all the devices you want to insert

(when the memory available is exhausted this is indicated with the message "PR010/T
memory completely filled!!").

6. Select Program/From configuration on the PR010/T menu.
7. Now go to the PR010/T unit and select the 4.Update SW menu from the main menu. This

message will appear: 

‘Update SW’

‘ENTER to confirm’

8. Press ENTER on the SACE PR010/T unit to display the following message:

’Waiting SW update’

9. Before one minute elapses, press OK in the window displayed on the PC. The SACE

PR010/T unit will now display the message:

‘SW Updating in progress’

accompanied by a progressive status bar indicating the download time remaining. The
maximum duration of the procedure may be several minutes, depending on the number of
devices selected; the "programming status" bar is displayed on the PC monitor in the
"Program PR010/T" window, indicating how the updating is proceeding. If the file is
successfully downloaded, the SACE PR010/T unit will display the following message:

“End SW updating”

“SW Ver. X.X”

“Press ESC to restart”

while the PC will display the message:

“PR010/T successfully programmed”

Press ESC on the SACE PR010/T unit to restart the unit with the new software version.
Close the PC application.

10. If the file is not successfully downloaded, the SACE PR010/T unit will display the

following message:

'WARNING.SW updating failed'

'Press ESC to restart'

and the PC will display the message:

'Time out error: cannot contact PR010/T'

11. Press ESC on the SACE PR010/T unit to return to the screen:

‘Program failed’

‘ENTER for recovery’

12. Select PROGRAM/from CONFIGURATION in the "PR010/T Program" of the PC. 

Summary of Contents for SACE PR010/T

Page 1: ...DOCUMENTATION CONTENTS This document is composed by 2 section Section Name Description 1 Instruction Main features and functions of PR010 T unit 2 Updating Additional information and or correction of...

Page 2: ...ABB SACE SACE PR010 T RH0025002 L2551 EN SACE PR010 T test unit instructions...

Page 3: ...test 6 4 1 3 Communication functions test 7 4 2 Programming function 7 4 3 Parameter reading function 7 4 4 Protection unit interface 8 4 5 PC interface 8 4 6 Test report 8 4 7 Special functions 10 5...

Page 4: ...6 Technical specifications 14 6 1 User interface 14 6 2 Power supply 14 6 3 Inputs Outputs 15 6 4 Mechanical specifications 16 6 5 Standard equipment 16 6 6 Applicable standards 17 6 7 Error messages...

Page 5: ...t in damp or wet environments If in doubt about the safety of the unit take it out of service to prevent inadvertent usage The unit s safety may be impaired if 1 the unit shows visible signs of damage...

Page 6: ...loaded from the ABB Internet site it is possible to upgrade the software of the SACE PR010 T unit The unit can also save important test results which may then be downloaded to a PC following a request...

Page 7: ...it can still operate if connected to the external power supply 3 3 General description 1 Cable connector for connection to circuit breaker protection unit 2 Backlit LCD display 4 x 20 character lines...

Page 8: ...be tested is simulated In case of units provided with internal bus the internal status of the protections alarm and trip messages etc may also be monitored In case of certain releases the type of rel...

Page 9: ...akers can be programmed You can also program all the protection function parameters threshold curve interlock parameters etc The parameter programming function does not interrupt the normal operation...

Page 10: ...lts in order to compile a test report The unit can store up to five test reports After the test reports have been downloaded in the PC it is advisable to delete them from the PR010 T so as to have eno...

Page 11: ...nt In 2 40 Expected time s 0 750 Measured time s 0 758 Test result OK Protection S Threshold In 0 800 Curve s 0 35 Curve type t k i 2 Tested phase s L1 Fault current In 1 60 Expected time s 13 668 Mea...

Page 12: ...that may be electronically programmed Define default The manual test function also enables a general current to be introduced into the release in order to test the trip time a particularly useful fun...

Page 13: ...Reset password item and notify ABB SACE of the code displayed e g CODE 63795 ABB SACE will provide an unlock code to input on the same page PLEASE INSERT RESET CODE which enables you to reset the PR0...

Page 14: ...unit to display the following message Waiting SW update 9 Before one minute elapses press OK in the window displayed on the PC The SACE PR010 T unit will now display the message SW Updating in progres...

Page 15: ...7 The SACE PR010 T unit will now display the message Download in progress accompanied by a progressive status bar indicating the download time remaining The maximum transmission duration is about one...

Page 16: ...meric display membrane keyboard and indicator led Each time a key is pressed an acoustic signal is emitted The back lit LCD display features 4 lines each containing up to 20 characters The display s b...

Page 17: ...unit switched off The batteries recharge automatically when the SACE PR010 T test unit is connected to the external power supply The rechargeable batteries are supplied discharged The batteries must t...

Page 18: ...Weight complete with rechargeable batteries 600 g Operating temperature range 0 C 50 0 C Storage temperature range 20 C 70 0C Maximum relative humidity 90 non condensing MTBF 15 years 30 C 1 SACE PR0...

Page 19: ...0 T connection and the name of the loaded file COMMUNICATION ERROR Communication error Press ESC to return This message indicates that the SACE PR010 T s internal bus is unable to establish a connecti...

Page 20: ...unit with the power supply provided by ABB SACE The external power supply is not connected to the mains power supply Connect the power supply to a 220V power mains No batteries fitted Fit batteries li...

Page 21: ...the required software version and repeat the update procedure The wrong type of file is selected Select file type PR010t_x Hex The file downloaded is damaged Use a spare copy or download the updated...

Page 22: ...s mechanical electrical and electronic and overall dimensions indicated in this handbook are only deemed legally binding subject to confirmation by ABB SACE The test unit does not need recalibrating W...

Page 23: ...p or more recent Windows 10 Administrator user Administrator user ERROR MESSAGES TROUBLESHOOTING Updating of faults described in chap 6 7 of Instruction RH0025002 N Faults Causes and errors Checks and...

Reviews: