ABB | SACE Emax 2
Ekip Touch protection trip unit | 13 - G Hi-Touch protections
97 | © 2017 ABB | 1SDH001330R0002 - ECN000058721 Rev. A
ROCOF Protection
f28
t
t28
Hz/s
ROCOF
Path
Main page - Menu - Advanced
Function
ROCOF protection protects against rapid frequency variations.
When the frequency change exceeds the control threshold f28 over time, the protection trips within a fixed
time t28.
It is also possible to characterize the protection according to the way in which frequency varies (increase or
decrease), or to consider both conditions.
f(Hz)
Time
failure
50/60 Hz
frequency
after failure
frequency
after failure
Figure 25
NOTE:
the protection is not active for voltages <30V.
Parameters
It is possible to modify various parameters:
Parameter
Description
Enable
To activate/deactivate the protection.
Threshold f28
It defines the maximum allowed frequency variation rate over time, above which
the protection will be activated.
It is represented as an absolute value (Hertz / second).
Trip Direction
It defines whether the protection monitors increases, decreases, or both
variations.
Time t28
This is the delay time between the exceeding of the f28 threshold and the
sending of the opening command
ROCOF protection has
StartUp enable
Via Ekip Connect it is also possible to access the
blocking functions
, see page 72.
Summary of Contents for SACE Emax E1.2
Page 2: ...ABB SACE Emax 2 2 2017 ABB 1SDH001330R0002 ECN000058721 Rev A ...
Page 8: ...VI 2017 ABB SACE Emax 2 1SDH001330R0002 ECN000058721 Rev A ...
Page 9: ...ABB SACE Emax 2 3 2017 ABB 1SDH001330R0002 ECN000058721 Rev A ...
Page 310: ...ABB SACE Emax 2 304 2017 ABB 1SDH001330R0002 ECN000058721 Rev A Service 1 Power Care ...