54
INSTRUCTION HANDBOOK
IEC version - Current rating up to 3200A
Tools
Torx key
No. 40
207
By means of the torx key (size 40) unscrew
the 6 screws fixing the terminals and their
protections to the pole.
209
Manually separate the terminals and their
protections.
208
Manually remove the terminals and their
protections.
Disassembly operations illustrated at pictures 207, 208 and 209 must be performed on the
other 2 poles.
Circuit breakers in IEC version characterized by a current rating up to 3200A show differences
at level of parts involved in this disassembly phase, consequently here below an analogous
section is provided for these circuit breakers.