ABB | SACE Emax 2
Management operations
3 - Description
22 | © 2023 ABB | 1SDH001000R0002 - ECN000297030
Continued from the previous page
Always use both levers of the guides on the fixed part when racking out the circuit-breaker. See Figure 50.
NO!
OK
=
=
Figure 51
WARNING! When withdrawing the moving part, make sure that both guides on the fixed
part travel to the same extent, thereby keeping the moving part parallel to the fixed
part. See Figure 51.
Mechanical position indicators
The following are the possible positions where you can find the mobile part of a withdrawable circuit-
breaker during its use:
• circuit breaker in DISCONNECT position (see Figure 52)
• circuit-breaker in test position (see Figure 53)
• circuit-breaker in CONNECT position (see Figure 54)
Figure 52
Figure 53
Figure 54