Connections and Settings  
Communication Unit 560CMD11 

 

Doc.-No.: 1KGT 150 765 V005 1 

 

 

Settings 

Hardware settings and operation of the communi-
cation Interfaces of the 560CMD11 are carried out 
with the RTUtil560 configuration tool. For the con-
figuration  procedure  of  the  communication  Inter-
faces  and  the  IO-Bus,  please  refer  to  the 
560RTUtil user guide. 

The  following  parameters  have  to  be  defined  for 
all protocols: 

 

Baudrate: 

 50  to 19 200 baud Mo-

dem control: 

 

Direct link (TxD/RxD only) 

 

WT  link  full  duplex  (560FSM10/11  no 
handshake)  

 

WT  link  half  duplex  (560FSM10/11  with 
RTS / DCD) 

 

Dial  up  (external  modem  without  hand-
shake, without RTS / CTS) 

 

Loop  switch  unit  (RP570/71  Host  Inter-
face only) 

 

Link  with  collision  avoidance  (TxD,  RxD, 
DCD, without handshake (DNP 3.0 only) 

 

The settings of the Ethernet Interface are: 

 

Node name 

 

IP address 

 

Subnet mask 

 

Default gateway 

 

Routing information 

 

The number of the host Interface. 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Fig. 6: 560ANA02 

 

 

For  the  configuration  procedure  of  the  GPRS-
Modem (only R0011),  please refer to the  function 
description part 6. 

The settings of the GPRS-Modem are: 

 

Local IP address 

 

Remote network IP address 

 

PIN number SIM-Card 

 

Username 

 

User password 

 

Provider Connectionstring (APN) 

 

RF sensitivity (only R0011) 

 

Main  parameters  for  the  transmitter 
are:  

  Max. output power: 30dBm ± 5dB  

  Min. output power:  0dBm ±5dB  

 

min.  signal  level  at  input  of  GPRS-
Chip: -108dBm 

 

cable  RG58  with  losses  of  0,546dB/m 

 10,92dB (20m) 

 

antenna with a gain of 2,2dBi 

 

Exemplary calculation: 

min. signal (receive) with 20m cable = 
-109dB + 10,92dB 

– 2,2dBr =  

-99,28dBm 

result:  the  RF  signal  at  the  point  of 
antenna shall be min. -99,28dBm 

Summary of Contents for RTU560

Page 1: ...8 has to be switched ON The 560CMD11 starts with the factory settings for the Ethernet Interface see Fig 2 which are 192 168 0 1 for the IP address with the network setting 255 255 255 0 for the subnet mask and 192 168 0 20 for the gateway Switch Def IP Address position OFF E Read IP address from confi guration file ON Set Switch Def IP Address to OFF Send Configuration to RTU 192 168 0 1 Switch D...

Page 2: ...er based protocols GPRS Modem Interface Both functions are mutually exclusive GPRS Modem only R0011 The settings have to be done by the RTUtil560 configuration tool The 560CMD11 R0011 provides a radio interface via an integrated Quad Band GSM GPRS mo dem For communication via the GSM GPRS mo dem a pluggable SIM Card is necessary The SIM Card socket is placed below the Com pactFlash socket The Quad...

Page 3: ...is 24VDC The connector consists of a 3 pole pluggable screw terminal 5 08mm see Tab 4 and Fig 8 or Fig 11 The max input power is 67 Watt In some cases an external potential isolation for the DC Input is neces sary This can be done e g by a power supply unit 560PSU40 41 Power Supply DC Out The 560CMD11 provides 24VDC output power for max 0 5A The connector consists of a 3 pole pluggable screw termi...

Page 4: ...onal galvanic isolated RS232 interface see Fig 5 if the entire system is grounded positively Signaling The red LED of the 560CMD11 is controlled by the RTU560 firmware For the definition and oper ation of the LED ERR please refer to the release specific function description The connector em bedded LEDs Tx and Rx are directly connected to the receiver transmitter of the communication line The LEDs ...

Page 5: ...on Unit 560CMD11 Doc No 1KGT 150 765 V005 1 5 Fig 4 Negative System Earthing Fig 5 Positive System Earthing power supply System 560CMD11 GPRS Chip RS232 560PSU40 41 RS232 galvanic isolated power supply System 560CMD11 GPRS Chip RS232 560PSU40 41 ...

Page 6: ... see Fig 8 and Fig 11 4 Pull or plug only the CF card Don t touch other components 5 Close the housing before the power supply is connected to the 560CMD11 SIM Card only R0011 For communication via the GSM GPRS modem a pluggable SIM Card ID 000 is necessary For changing the SIM Card the right side of the housing has to be opened see Fig 11 1 Disconnect the power supply of the 560CMD11 2 Take care ...

Page 7: ... with collision avoidance TxD RxD DCD without handshake DNP 3 0 only The settings of the Ethernet Interface are Node name IP address Subnet mask Default gateway Routing information The number of the host Interface Fig 6 560ANA02 For the configuration procedure of the GPRS Modem only R0011 please refer to the function description part 6 The settings of the GPRS Modem are Local IP address Remote net...

Page 8: ...and Settings Communication Unit 560CMD11 Doc No 1KGT 150 765 V005 1 8 Fig 7 Top side of 560CMD11 R0001 housing screws screws Fig 8 Front and right side of 560CMD11 R0001 housing Fig 9 Bottom side of 560CMD11 R0001 housing ...

Page 9: ...ttings Communication Unit 560CMD11 Doc No 1KGT 150 765 V005 1 9 Ethernet Fig 10 Top side of 560CMD11 R0011 housing Fig 11 Front and right side of 560CMD11 R0011 housing screws screws Fig 12 Bottom side of 560CMD11 R0011 housing ...

Page 10: ...eed particulars shall prevail ABB AG does not accept any responsibility whatsoever for potential errors or possible lack of information in this document We reserve all rights in this document and in the subject matter and illustrations contained therein Any reproduction disclosure to third parties or utilization of its contents in whole or in parts is forbidden without prior written consent of ABB...

Reviews: