10
RS85
VIBR ATING FORK LEVEL SWITCH | OI/RS85-EN REV. K
Accessing setup adjustments
3 Setup (Configuring Switch)
Setup of the RS85 may be achieved using a (1) magnet
(provided with switch) positioned on the housing or (2) by
means of the pushbuttons on the module. In the following
operations, pushbuttons (Figure 19) will correspond to
magnet positions (Figure 20) as follows:
S1 position = S1 button only
S2 position = S2 button only
X position = S1 and S2 simultaneously
During normal operation, LED1 will light either RED or GREEN
based on the settings of the switch.
Initial setup instructions:
Step 1:
RS85 (resets to factory defaults)
Power up the electronic module with it disconnected
from the fork assembly (Figure 21). Press S1 and S2
buttons of the electronic module and hold for several
Seconds while a sequence of red and green lights display
ending with LED1 RED (Figure 21). The RS85 electronic
module is now set to factory defaults. Re–install the
electronic module in the fork assembly.
LED 1
LED 2
S2 pushbutton
Power
input
S1
pushbutton
Power
requirement
Relay
RS85
magnet
position
label
Figure 19
Figure 20