2.4.4.4
LD0.LSHDPFRQ4 Load shedding controls (4)
Table 80:
LD0.LSHDPFRQ4 Load shedding controls (4)
IEC 61850 name
SA name
Description
Type
LD0.LSHDPTRC4
.ManRest.Oper.ctlVal
MAN_RESTORE
Manual restore
On
.BlkRest.Oper.ctlVal
BLK_REST
Cancel restore
On
2.4.4.5
LD0.LSHDPFRQ5 Load shedding controls (5)
Table 81:
LD0.LSHDPFRQ5 Load shedding controls (5)
IEC 61850 name
SA name
Description
Type
LD0.LSHDPTRC5
.ManRest.Oper.ctlVal
MAN_RESTORE
Manual restore
On
.BlkRest.Oper.ctlVal
BLK_REST
Cancel restore
On
2.4.5
Protection-related functions
2.4.5.1
DR.RDRE1 Disturbance recorder
Table 82:
DR.RDRE1 Disturbance recorder
IEC 61850 name
SA name
Description
Type
DR.RDRE1
.MemClr.Oper.ctlVal
-
Clear all records
On
.RcdTrg.Oper.ctlVal
-
Trig recording
On
2.4.6
Generic functions
2.4.6.1
LD0.SPCGGIO1 Multipurpose binary outputs (1)
The binary outputs may be configured either as pulse- or persistent-type outputs.
Pulse-type outputs are triggered with the write value "1". Persistent-type outputs
can be written with both "1" and "0" values. The persistent type is the same as the
toggled mode on LHMI and WHMI.
Table 83:
LD0.SPCGGIO1 Multipurpose binary outputs (1)
IEC 61850 name
SA name
Description
Type
LD0.SPCGGIO1
.SPCS01.ctlVal
-
Output 1 control
On/Off
.SPCS02.ctlVal
-
Output 2 control
On/Off
.SPCS03.ctlVal
-
Output 3 control
On/Off
Table continues on next page
Section 2
1MRS757056 C
DNP3 data mappings
36
REU615
Point List Manual