Terminal
Description
X110-21
SO3, NO
X110-22
SO3, NC
X110-23
SO4, common
X110-24
SO4, NO
Output contacts of slot X130 are available in the optional BIO module (BIOB02A).
Output contacts of slot X130 are optional for configuration B.
Table 36:
Output contacts X130-10...18
Terminal
Description
X130-10
SO1, common
X130-11
SO1, NO
X130-12
SO1, NC
X130-13
SO2, common
X130-14
SO2, NO
X130-15
SO2, NC
X130-16
SO3, common
X130-17
SO3, NO
X130-18
SO3, NC
5.2.3
IRF
The IRF contact functions as an output contact for the self-supervision system of
the protection IED. Under normal operating conditions, the IED is energized and
the contact is closed (X100/3-5). When a fault is detected by the self-supervision
system or the auxiliary voltage is disconnected, the output contact drops off and the
contact closes (X100/3-4).
Table 37:
IRF contact
Terminal
Description
X100-3
IRF, common
X100-4
Closed; IRF, or U
aux
disconnected
X100-5
Closed; no IRF, and U
aux
connected
Section 5
1MRS757054 A
IED physical connections
68
REU615
Application Manual