Functionality
IEC 61850
IEC 60617
IEC-ANSI
Master trip, instance 2
TRPPTRC2
Master Trip (2)
94/86 (2)
Multi-purpose protection, instance 1 MAPGAPC1
MAP (1)
MAP (1)
Multi-purpose protection, instance 2 MAPGAPC2
MAP (2)
MAP (2)
Multi-purpose protection, instance 3 MAPGAPC3
MAP (3)
MAP (3)
Control
Circuit-breaker control
CBXCBR1
I <-> O CB
I <-> O CB
Disconnector position indication,
instance 1
DCSXSWI1
I <-> O DC (1)
I <-> O DC (1)
Disconnector position indication,
instance 2
DCSXSWI2
I <-> O DC (2)
I <-> O DC (2)
Disconnector position indication,
instance 3
DCSXSWI3
I <-> O DC (3)
I <-> O DC (3)
Earthing switch indication
ESSXSWI1
I <-> O ES
I <-> O ES
Tap changer position indication
TPOSSLTC1
TPOSM
84M
Tap changer control with voltage
regulator
OLATCC1
COLTC
90V
Condition monitoring
Trip circuit supervision, instance 1
TCSSCBR1
TCS (1)
TCM (1)
Trip circuit supervision, instance 2
TCSSCBR2
TCS (2)
TCM (2)
Current circuit supervision
CCRDIF1
MCS 3I
MCS 3I
Fuse failure supervision
SEQRFUF1
FUSEF
60
Measurement
Disturbance recorder
RDRE1
-
-
Three-phase current measurement,
instance 1
CMMXU1
3I
3I
Sequence current measurement
CSMSQI1
I1, I2, I0
I1, I2, I0
Three-phase voltage measurement
VMMXU1
3U
3U
Sequence voltage measurement
VSMSQI1
U1, U2, U0
U1, U2, U0
Three-phase power and energy
measurement, including power
factor
PEMMXU1
P, E
P, E
RTD/mA measurement
XRGGIO130
X130 (RTD)
X130 (RTD)
3.5.2.1
Default I/O connections
Table 15:
Default connections for binary inputs
Binary input
Default usage
Connector pins
X110-BI1
Tap changer operates
X110-1,2
X110-BI2
Voltage transformer secondary MCB open
X110-3,4
X110-BI3
Lower local request
X110-5,6
X110-BI4
Raise local request
X110-7,6
Table continues on next page
1MRS757054 A
Section 3
REU615 standard configurations
REU615
45
Application Manual