21
1. Press an arrow button to access the main menu
2. Use the arrow buttons to select
CONFIGURATION\COMMUNICATION\SPA
SETTINGS\PASSWORD SPA
and press
.
3. Press
to enter the setting mode and give the current HMI password if
required. If the default password 999 is still valid, no password is required.
4. The first digit of the password to be edited starts to flash. Set the digit using
and
.
5. Activate the next digit to be set by pressing
or
.
6. To store the new SPA password and return the display to the view mode, press
. The display confirms the storage by flashing "
- - -
" once on the display.
Alternatively, to exit the setting mode without storing the SPA password change,
press
once before confirming and the display returns to the view mode.
7. Press
to return the display to the idle mode.
HMI PASSWORDS
TIME
LINE-IDLE STATE
CONNECTION TYPE
TRIP CIRCUIT SUP
Main Menu
Group Menu
Parameter Menus
SETTINGS
CONFIGURATION
MEASUREMENTS
RECORDED DATA
COUNTER :000
UNIT ADDRESS :000
MODBUS SETTINGS
SPA SETTINGS
REAR PROTOCOL
FREQUENCY
CONFIGURATION
FUNCTION TEST/DI
COMMUNICATION
LANGUAGE
REAR CONNECTION
CONFIGURATION
MEMORY SETTINGS
IEC103 SETTINGS
PASSWORD SPA :000
CONFIGURATION
REAR COM. MODULE
Confirm
Cancel
Scroll for the digit
Set the digit
INFO
U NOMINAL
OPERATION
STORE COUNTER
A051584_2
Fig. 4.1.7.-1
Changing SPA password
4.1.8.
How to select language
The relay allows you to choose among several different languages. The default
language is English.
Change the display language as follows:
1. Press an arrow button to access the main menu.
2. Use the arrow buttons to select
CONFIGURATION\LANGUAGE
and press
to
enter the currently valid language.
3. Press
to enter the setting mode and give the password if required. The second
line starts to flash indicating that you are allowed to set the language.
4. Use
or
to move the cursor to the wanted language.
Voltage Protection Relay
Operator's Manual
REU 610
REU 610
1MRS755770