Section 19
Technical data
19.1
Dimensions
Table 537:
Dimensions of the IED - 3U full 19" rack
Description
Value
Width
444 mm (17.48 inches)
Height
132 mm (5.20 inches), 3U
Depth
249.5 mm (9.82 inches)
Weight box
10 kg (<22.04 lbs)
19.2
Power supply
Table 538:
Power supply
Description
PSM01
PSM02
PSM03
U
aux
nominal
24, 30V DC
48, 60, 110, 125 V DC
100, 110, 120, 220,
240 V AC, 50 and 60
Hz
110, 125, 220, 250 V
DC
U
aux
variation
80...120% of U
n
(19.2...36 V DC)
80...120% of U
n
(38.4...150 V DC)
80...110% of U
n
(80...264 V AC)
80...120% of U
n
(88...300 V DC)
Maximum load of
auxiliary voltage supply
35 W for DC
40 VA for AC
Ripple in the DC
auxiliary voltage
Max 15% of the DC value (at frequency of 100 and 120 Hz)
Maximum interruption
time in the auxiliary DC
voltage without resetting
the IED
50 ms at U
aux
Resolution of the
voltage measurement in
PSM module
1 bit represents 0,5 V
(+/- 1 VDC)
1 bit represents 1 V (+/-
1 VDC)
1 bit represents 2 V (+/-
1 VDC)
1MRK 504 135-UEN A
Section 19
Technical data
615
Technical manual