Section 13
Logic
13.1
Tripping logic common 3-phase output SMPPTRC
13.1.1
Identification
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Tripping logic common 3-phase output
SMPPTRC
I->O
SYMBOL-K V1 EN
94
13.1.2
Functionality
A function block for protection tripping is provided for each circuit breaker involved
in the tripping of the fault. It provides a settable pulse prolongation to ensure a three-
phase trip pulse of sufficient length, as well as all functionality necessary for correct
co-operation with autoreclosing functions.
The trip function block also includes a settable latch functionality for breaker lock-
out.
13.1.3
Function block
SMPPTRC
BLOCK
TRIN
SETLKOUT
RSTLKOUT
TRIP
CLLKOUT
IEC09000284_1_en.vsd
IEC09000284 V1 EN
Figure 163:
SMPPTRC function block
1MRK 504 135-UEN A
Section 13
Logic
371
Technical manual