Current protection
Table 29. Instantaneous phase overcurrent protection, 3-phase output PHPIOC
Function
Range or value
Accuracy
Operate current
(5-2500)% of lBase
±
1.0% of I
r
at I
£
I
r
±
1.0% of I at I > I
r
Reset ratio
> 95%
-
Operate time
20 ms typically at 0 to 2 x I
set
-
Reset time
30 ms typically at 2 to 0 x I
set
-
Critical impulse time
10 ms typically at 0 to 2 x I
set
-
Operate time
10 ms typically at 0 to 5 x I
set
-
Reset time
40 ms typically at 5 to 0 x I
set
-
Critical impulse time
2 ms typically at 0 to 5 x I
set
-
Dynamic overreach
< 5% at
t
= 100 ms
-
Table 30. Four step phase overcurrent protection, 3-phase output OC4PTOC
Function
Setting range
Accuracy
Operate current
(5-2500)% of
lBase
±
1.0% of I
r
at I ≤ I
r
±
1.0% of I at I > I
r
Reset ratio
> 95% at (50–2500)% of
lBase
-
Min. operating current
(5-10000)% of
lBase
±
1.0% of I
r
at I ≤ I
r
±
1.0% of I at I > I
r
2nd harmonic blocking
(5–100)% of fundamental
±
2.0% of I
r
Independent time delay
(0.000-60.000) s
±
0.5%
±
25 ms
Minimum operate time for inverse
characteristics
(0.000-60.000) s
±
0.5%
±
25 ms
Inverse characteristics, see
table
15 curve types
1)
ANSI/IEEE C37.112
IEC 60255–151
±
3% or
±
40 ms
0.10 ≤ k ≤ 3.00
1.5 x I
set
≤ I ≤ 20 x I
set
Operate time, nondirectional start
function
25 ms typically at 0 to 2 x I
set
-
Reset time, nondirectional start
function
35 ms typically at 2 to 0 x I
set
-
Operate time, directional start
function
50 ms typically at 0 to 2 x I
set
-
Reset time, directional start
function
35 ms typically at 2 to 0 x I
set
-
Critical impulse time
10 ms typically at 0 to 2 x I
set
-
Impulse margin time
15 ms typically
-
1)
Note: Timing accuracy only valid when 2nd harmonic blocking is turned off
Transformer protection RET650
1MRK 504 137-BEN B
Product version: 1.3
ABB
41