24
1MRS755225
Transformer Terminal
Technical Reference Manual, General
RET 54_
5. Technical
Description
5.1.
Functional description
5.1.1.
Functions of the transformer terminal
The functions of the RET 54_ transformer terminal are categorized as:
• Protection functions
• measurement functions
• control functions
• condition monitoring functions
• communication functions
• general functions
• standard functions
The functions are further divided to three subsets that correspond to different
functionality levels (refer to Section “Ordering Information” on page 103).
5.1.1.1.
Protection functions
Protection is one of the most important functions of the RET 54_ transformer
terminal. The protection function blocks (e.g. NOC3Low) are independent of each
other and have e.g. their own setting groups and data recording.
The protection function blocks are documented on the CD-ROM “Technical
Descriptions of Functions” (refer to “Related documents” on page 9).
Table 5.1.1.1-1
Protection functions available for the RET 54_
Function
Description
DEF2Low
Directional earth-fault protection, low-set stage
DEF2High
Directional earth-fault protection, high-set stage
DEF2Inst
Directional earth-fault protection, instantaneous stage
Diff6T
Stabilized three-phase differential protection for transformers
DOC6Low
Three-phase directional overcurrent protection, low-set stage
DOC6High
Three-phase directional overcurrent protection, high-set stage
DOC6Inst
Three-phase directional overcurrent protection, instantaneous stage
Freq1St1
Underfrequency or overfrequency protection, stage 1
Freq1St2
Underfrequency or overfrequency protection, stage 2
Freq1St3
Underfrequency or overfrequency protection, stage 3
Freq1St4
Underfrequency or overfrequency protection, stage 4
Freq1St5
Underfrequency or overfrequency protection, stage 5
FuseFail
Fuse failure supervision
Inrush3
Three-phase transformer inrush and motor start-up current detector
NEF1Low
Non-directional earth-fault protection, low-set stage
NEF1High
Non-directional earth-fault protection, high-set stage
NEF1Inst
Non-directional earth-fault protection, instantaneous stage
NOC3Low
Three-phase non-directional overcurrent protection, low-set stage
NOC3LowB
Three-phase non-directional overcurrent protection, low-set stage B
NOC3High
Three-phase non-directional overcurrent protection, high-set stage
NOC3Inst
Three-phase non-directional overcurrent protection, instantaneous stage