Section 7
1MAC309294-MB F
Measurement functions
398
RER620
Technical Manual
7.1.6
Ground current IG
7.1.6.1
Identification
7.1.6.2
Function block
Figure 212:
Function block
7.1.6.3
Signals
Table 351: IG Input signals
Table 352: IG Output signals
7.1.6.4
Settings
Table 353: IG Non group settings
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Neutral current
RESCMMXU
I0
IG
Name
Type
Default
Description
IG
SIGNAL
0
Ground current
BLOCK
BOOLEAN
0=False
Block signal for all binary outputs
Name
Type
Description
HIGH_ALARM
BOOLEAN
High alarm
HIGH_WARN
BOOLEAN
High warning
Parameter
Values (Range) Unit Step Default
Description
Operation
1=Enable
5=Disable
1=Enable
Operation Off / On
Measurement mode
1=RMS
2=DFT
2=DFT
Selects used measurement mode
A Hi high limit res
0.00...40.00
xIn
0.20
High alarm current limit
A high limit res
0.00...40.00
xIn
0.05
High warning current limit
A deadband res
100...100000
2500
Deadband configuration value for integral calculation. (percentage of
difference between min and max as 0,001% s)
Summary of Contents for RER620
Page 2: ......
Page 22: ...Section 1MAC309294 MB F 16 RER620 Technical Manual ...
Page 88: ...Section 3 1MAC309294 MB F Basic functions 82 RER620 Technical Manual ...
Page 278: ...Section 4 1MAC309294 MB F Protection functions 272 RER620 Technical Manual ...
Page 362: ...Section 5 1MAC309294 MB F Control functions 356 RER620 Technical Manual ...
Page 418: ...Section 7 1MAC309294 MB F Measurement functions 412 RER620 Technical Manual ...
Page 428: ...Section 8 1MAC309294 MB F Recording functions 422 RER620 Technical Manual ...
Page 464: ...Section 9 1MAC309294 MB F Other functions 458 RER620 Technical Manual ...
Page 554: ...Section 10 1MAC309294 MB F General function block features 548 RER620 Technical Manual ...
Page 568: ...Section 12 1MAC309294 MB F Relay physical connections 562 RER620 Technical Manual ...
Page 574: ...Section 13 1MAC309294 MB F Technical data 568 RER620 Technical Manual ...
Page 576: ...Section 14 1MAC309294 MB F Relay and functionality tests 570 RER620 Technical Manual ...
Page 578: ...Section 15 1MAC309294 MB F Applicable standards and regulations 572 RER620 Technical Manual ...
Page 582: ...Section 16 1MAC309294 MB F Glossary 576 RER620 Technical Manual ...
Page 583: ......