1MAC309294-MB F
Section 4
Protection functions
RER620
215
Technical Manual
the closure of the circuit breaker if the 47 operation has started. This scheme also prevents
connecting the machine to the network if the phase sequence of the network is not correct.
An appropriate value for the setting parameter
Voltage pickup value
is approximately 3
percent of V
n
. A suitable value for the setting parameter
Trip delay time
depends on the
application. If the 47 operation is used as a backup protection, the trip time should be set
in accordance with the trip time of 46 used as the main protection. If the 47 operation is
used as the main protection, the trip time should be approximately one second.
4.3.5.6
Signals
Table 228: 47 Input signals
Table 229: 47 Output signals
4.3.5.7
Settings
Table 230: 47 Group settings
Table 231: 47 Non group settings
4.3.5.8
Monitored data
Table 232: 47 Monitored data
Name
Type
Default
Description
V
2
SIGNAL
0
Negative phase sequence voltage
BLOCK
BOOLEAN
0=False
Block signal for activating the blocking mode
Name
Type
Description
TRIP
BOOLEAN
Trip
PICKUP
BOOLEAN
Pickup
Parameter
Values (Range)
Unit
Step
Default
Description
Pickup value
0.010...1.000
xVn
0.001
0.030
Pickup value
Trip delay time
40...120000
ms
1
40
Trip delay time
Parameter
Values (Range)
Unit
Step
Default
Description
Operation
1=Enable
5=Disable
5=Disable
Operation Disable / Enable
Reset delay time
0...60000
ms
1
20
Reset delay time
Name
Type
Values (Range)
Unit
Description
PICKUP_DUR
FLOAT32
0.00...100.00
%
Ratio of pickup
time / trip time
47
Enum
1=enabled
2=blocked
3=test
4=test/blocked
5=disabled
Status
Summary of Contents for RER620
Page 2: ......
Page 22: ...Section 1MAC309294 MB F 16 RER620 Technical Manual ...
Page 88: ...Section 3 1MAC309294 MB F Basic functions 82 RER620 Technical Manual ...
Page 278: ...Section 4 1MAC309294 MB F Protection functions 272 RER620 Technical Manual ...
Page 362: ...Section 5 1MAC309294 MB F Control functions 356 RER620 Technical Manual ...
Page 418: ...Section 7 1MAC309294 MB F Measurement functions 412 RER620 Technical Manual ...
Page 428: ...Section 8 1MAC309294 MB F Recording functions 422 RER620 Technical Manual ...
Page 464: ...Section 9 1MAC309294 MB F Other functions 458 RER620 Technical Manual ...
Page 554: ...Section 10 1MAC309294 MB F General function block features 548 RER620 Technical Manual ...
Page 568: ...Section 12 1MAC309294 MB F Relay physical connections 562 RER620 Technical Manual ...
Page 574: ...Section 13 1MAC309294 MB F Technical data 568 RER620 Technical Manual ...
Page 576: ...Section 14 1MAC309294 MB F Relay and functionality tests 570 RER620 Technical Manual ...
Page 578: ...Section 15 1MAC309294 MB F Applicable standards and regulations 572 RER620 Technical Manual ...
Page 582: ...Section 16 1MAC309294 MB F Glossary 576 RER620 Technical Manual ...