Table 28. 46PD technical data
—
Table 29. Three-phase inrush current detection (INR)
Characteristic
Value
Operation accuracy
Depending on the frequency of the current
measured: f
n
±2Hz
±2% of the set value
Pickup time
< 70 ms
Reset time
< 40 ms
Reset ratio
Typical 0.96
Retardation time
< 35 ms
Trip time accuracy in definite time mode
±1.0% of the set value or ±20 ms
Suppression of harmonics
DFT: -50dB at f = n x f
n
, where n = 2, 3, 4, 5,…
Characteristic
Value
Pickup accuracy
At the frequency f=f
n
Current measurement:
±1.5% of set value or ±0.002 x I
n
Ratio I2f/I1f measurement: ±5.0% of set value
Reset time
+35 ms / -0 ms
Reset ratio
Typical 0.96
Trip time accuracy
+35 ms / -0 ms
—
Table 30. 59 technical data
Characteristic
Value
Operation accuracy
Depending on the frequency of the current measured: f
n
±2Hz
±1.5% of the set value or ±0.002 x V
n
Pickup time
1) 2)
V
Fault
= 1.1 x set Pickup value
Minimum
Typical
Maximum
22 ms
24 ms
26 ms
Reset time
< 40 ms
Reset ratio
Depends on the Relative hysteresis
Retardation time
< 35 ms
Trip time accuracy in definite time mode
±1.0% of the set value or ±20 ms
Trip time accuracy in inverse time mode
±5.0% of the theoretical value or ±20 ms
3)
Suppression of harmonics
DFT: -50dB at f = n x f
n
, where n = 2, 3, 4, 5,…-
1)
Pickup value = 1.0 x V
n
, Voltage before fault 0.9 x V
n
, f
n
= 60 Hz, overvoltage in one phase-to-phase with nominal frequency injected from random phase angle, results based on sta
-
tistical distribution of 1000 measurements
2)
Includes the delay of the signal output contact
3)
Maximum Pickup value = 1.20 x V
n
, Pickup range multiples in range of 1.10 to 2.00