IEC13000062-1-en.vsd
IEC13000062 V1 EN-US
Figure 8:
Select: Use the following IP address
7.
Close all open windows and start PCM600.
Setting up the PC to access the IED via a network
This task depends on the used LAN/WAN network.
The PC and IED must belong to the same subnetwork for this set-up to work.
4.6
Writing an application configuration to the IED
M11734-2 v5
Ensure that the IED includes the correct application configuration according to
project specifications.
The application configuration is created using PCM600 and then written to the IED. Establish a
connection between PCM600 and the IED when an application configuration must be written
to the IED.
After writing an application configuration to the IED, the IED makes an application restart or a
complete IED restart, when necessary.
The IED does not restart after reconfiguring IEC61850 (regardless of whether
the protocol is enabled or disabled).
Be sure to set the correct technical key in both the IED and PCM600 to prevent
writing an application configuration to a wrong IED.
Section 4
1MRK 505 293-UEN B
Starting up
30
Breaker protection REQ650
Commissioning manual
© Copyright 2013 ABB. All rights reserved