![ABB REM615 ANSI Manual Download Page 35](http://html.mh-extra.com/html/abb/rem615-ansi/rem615-ansi_manual_2834035.webp)
2.3.2.5
LD0.DNPGGIO1 Parameter setting group control
Table 65:
LD0.DNPGGIO1 Parameter setting group control
IEC 61850 name
SA name
Description
Type
LD0.DNPGGIO1
.ActSG1.ctlVal
-
Setting group 1
On
.ActSG2.ctlVal
-
Setting group 2
On
.ActSG3.ctlVal
-
Setting group 3
On
.ActSG4.ctlVal
-
Setting group 4
On
.ActSG5.ctlVal
-
Setting group 5
On
.ActSG6.ctlVal
-
Setting group 6
On
2.3.2.6
LD0.LLN0/LPHD1 Reset indications and LEDs, reset device
Table 66:
LD0.LLN0/LPHD1 Reset indications and LEDs, reset device
IEC 61850 name
SA name
Description
Type
LD0.LLN0
.LEDRs1.Oper.ctlVal
-
Reset indications and LEDs
On
.LEDRs2.Oper.ctlVal
-
Reset alarm LEDs
On
LD0.LPHD1
.RsDev.Oper.ctlVal
-
Reset device
On
2.3.2.7
LD0.PEMMXU1 Reset accumulated energy values
Table 67:
LD0.PEMMXU1 Reset accumulated energy values
IEC 61850 name
SA name
Description
Type
LD0.PEMMXU1
.SupDmdRs.Oper.ctlVal
RSTACM
Reset accum. energy
On
2.3.2.8
DR.RDRE1 Disturbance recorder
Table 68:
DR.RDRE1 Disturbance recorder
IEC 61850 name
SA name
Description
Type
DR.RDRE1
.MemClr.Oper.ctlVal
-
Clear all records
On
.RcdTrg.Oper.ctlVal
-
Trig recording
On
1MRS756880 C
Section 2
DNP3 data mappings
REM615
29
Point List Manual