![ABB REM615 ANSI Manual Download Page 24](http://html.mh-extra.com/html/abb/rem615-ansi/rem615-ansi_manual_2834024.webp)
2.3.1.17
LD0.LEDGGIO1 LHMI LED indications
Table 20:
LD0.LEDGGIO1 LHMI LED indications
IEC 61850 name
SA name
Description
Values
LD0.LEDGGIO1
.SPCSO1.stVal
-
LED 1 state
0/1=Off/On
.SPCSO2.stVal
-
LED 2 state
0/1=Off/On
.SPCSO3.stVal
-
LED 3 state
0/1=Off/On
.SPCSO4.stVal
-
LED 4 state
0/1=Off/On
.SPCSO5.stVal
-
LED 5 state
0/1=Off/On
.SPCSO6.stVal
-
LED 6 state
0/1=Off/On
.SPCSO7.stVal
-
LED 7 state
0/1=Off/On
.SPCSO8.stVal
-
LED 8 state
0/1=Off/On
.SPCSO9.stVal
-
LED 9 state
0/1=Off/On
.SPCSO10.stVal
-
LED 10 state
0/1=Off/On
.SPCSO11.stVal
-
LED 11 state
0/1=Off/On
2.3.1.18
LD0.LEDPTRC1 Global protection signals
Table 21:
LD0.LEDPTRC1 Global protection signals
IEC 61850 name
SA name
Description
Values
LD0.LEDPTRC1
Global protection signals
.Op.general
-
-General Operate
1=Operate
.Op.phsA
-
-phsA Operate
1=Operate
.Op.phsB
-
-phsB Operate
1=Operate
.Op.phsC
-
-phsC Operate
1=Operate
.Str.general
-
-General Start
1=Start
.Str.phsA
-
-phsA Start
1=Start
.Str.phsB
-
-phsB Start
1=Start
.Str.phsC
-
-phsC Start
1=Start
2.3.1.19
CTRL.LLN0 Local/remote state (also present in DNP IIN-bits)
Table 22:
CTRL.LLN0 Local/remote state (also present in DNP IIN-bits)
IEC 61850 name
SA name
Description
Values
CTRL.LLN0
.Loc.stVal
Remote/Local state
0/1=Rem/Loc
Section 2
1MRS756880 C
DNP3 data mappings
18
REM615