Description
HR/IR address
(.bit)
DI/Coil bit
address
Writeable
Value range Comment
Trip target code
814
0...21
See Table 5.1.15.-
2
Start-up time of the latest motor start
up
815
0...240
Seconds
Number of pickups of element 48/14
816
0...999
Counter
Number of pickups of element 50P-1
817
0...999
Counter
Number of pickups of element 51N
818
0...999
Counter
Number of pickups of element 37
819
0...999
Counter
Number of pickups of element 46
820
0...999
Counter
a)
During motor start up, the value 16383 will be returned, indicating that the current value is not available.
b)
During motor start up, the value 13107 will be returned, indicating that the current value is not available.
Table 5.1.14.1.-13
Mapping of Modbus data: control points
Description
HR/IR address
(.bit)
DI/Coil bit
address
Writeable
Value range Comment
LED reset
501
W
1
1 = LED reset
a)
a)
Coil area, only writeable.
Structure 1
The status registers contain information on unread fault and event records, and relay
status. The registers are arranged as in Fig. 5.1.14.1.-2 below.
401
402
403
15
8
7
0
Reserved
Warning
code
IRF
code
Reserved
FR ER
SP MP
A040333
Fig. 5.1.14.1.-2
Status registers
When the value of the FR/ER bit is 1, there is one or several unread fault/event
records. If time synchronization is realized via a digital input, either the SP (second-
pulse) or MP (minute-pulse) bit will be activated.
Refer to Table 5.1.16.-1 for IRF codes and Table 5.1.16.-2 for warning codes.
Structure 2
This structure contains data recorded during a fault sequence. Refer to Fault records
earlier in this section for the reading method.
86
REM 610
REM 610
Motor Protection Relay
Technical Reference Manual - ANSI Version
1MRS755537