Switch
Function
Default setting
SGR1...SGR2
SGR3
SGR4...SGR5
SGR1...5/6
Trip signal from element 50P
1
0
0
SGR1...5/7
Pickup signal from element 37
0
0
1
SGR1...5/8
Trip signal from element 37
1
0
0
SGR1...5/9
Pickup signal from element 51N
0
0
1
SGR1...5/10
Trip signal from element 51N
1
0
0
SGR1...5/11
Pickup signal from element 46
0
0
1
SGR1...5/12
Trip signal from element 46
1
0
0
SGR1...5/13
Pickup signal from element 46R
1
0
0
SGR1...5/14
Motor start-up signal
0
0
1
SGR1...5/15
External trip signal
0
0
0
SGR1...5/16
Alarm signal from element 49/38-1
0
0
0
SGR1...5/17
Trip signal from element 49/38-1
0
0
0
SGR1...5/18
Alarm signal from element 49/38-2
0
0
0
SGR1...5/19
Trip signal from element 49/38-2
0
0
0
Σ
SGR1...5
6826
0
9557
If the restart disable signal has been routed to PO3, SGR3 will be
overridden.
SGL1...SGL8
The signals are routed to LED1 with the switches of switchgroup SGL1, to LED2
with those of SGL2, and so forth.
Table 5.1.4.12.-9
SGL1...SGL8
Switch
Function
Default setting
SGL1
SGL2
SGL3...8
SGL1...8/1
Alarm signal from element 49
0
0
0
SGL1...8/2
Trip signal from element 49
0
0
0
SGL1...8/3
Restart disable signal
1
0
0
SGL1...8/4
Motor start up signal
0
1
0
SGL1...8/5
Trip signal from element (48/14 PICKUP)
2
x (48/14 TDLY) or 48/14
0
0
0
SGL1...8/6
Trip signal from element 50P
0
0
0
SGL1...8/7
Trip signal from element 37
0
0
0
SGL1...8/8
Trip signal from element 51N
0
0
0
SGL1...8/9
Trip signal from element 46
0
0
0
SGL1...8/10
Trip signal from element 46R
0
0
0
SGL1...8/11
Emergency start signal
0
0
0
SGL1...8/12
DI1 signal
0
0
0
56
REM 610
REM 610
Motor Protection Relay
Technical Reference Manual - ANSI Version
1MRS755537