149
Variable
Group/
Channel 2
(R, W, P)
Setting range
Default
setting
Customer
’
s
setting
Start-up current for motor or
start value of element 48/14
2S7
1.00
…
10.0 x FLA
1.00 x FLA
Start-up time for motor or
operate time of element 48/
14
2S8
0.30...80.0 s
0.30 s
Pickup value of element 50P 2S9
0.50...20.0 x FLA
1.00 x FLA
Operate time of element 50P 2S10
0.05...30.0 s
0.05 s
Pickup value of element 51N 2S11
1.0...100% I
n
CT
1.0% I
n
CT
Operate time of element 51N 2S12
0.05...300 s
0.05 s
Pickup value of element 51P 2S13
30...80% FLA
50% FLA
Operate time of element 51P 2S14
2...600 s
2 s
Pickup value of element 46 2S15
0.10
…
0.50 x FLA
0.20 x FLA
Time constant of element 46
at IDMT characteristic
2S16
5...100
5
Restart disable value
2S17
5...500 s
5 s
Countdown rate of start-up
time counter
2S18
2...250 s/h
2 s/h
Operate time of CBFAIL
2S19
0.10...60.0 s
0.10 s
Alarm value RTD1A
2S20
0...200°C
0°C
Operate time RTD1A TDLY
2S26
1...100 s
1 s
Trip value RTD1T
2S32
0...200°C
0°C
Operate time RTD1T TDLY
2S38
1...100 s
1 s
Alarm value RTD2A
2S21
0...200°C
0°C
Operate time RTD2A TDLY
2S27
1...100 s
1 s
Trip value RTD2T
2S33
0...200°C
0°C
Operate time RTD2T TDLY
2S39
1...100 s
1 s
Alarm value RTD3A
2S22
0...200°C
0°C
Operate time RTD3A TDLY
2S28
1...100 s
1 s
Trip value RTD3T
2S34
0...200°C
0°C
Operate time RTD3T TDLY
2S40
1...100 s
1 s
Alarm value RTD4A
2S23
0...200°C
0°C
Operate time RTD4A TDLY
2S29
1...100 s
1 s
Trip value RTD4T
2S35
0...200°C
0°C
Operate time RTD4T TDLY
2S41
1...100 s
1 s
Alarm value RTD5A
2S24
0...200°C
0°C
Operate time RTD5A TDLY
2S30
1...100 s
1 s
Trip value RTD5T
2S36
0...200°C
0°C
Operate time RTD5T TDLY
2S42
1...100 s
1 s
Alarm value RTD6A
2S25
0...200°C
0°C
Operate time RTD6A TDLY
2S31
1...100 s
1 s
Trip value RTD6T
2S37
0...200°C
0°C
Operate time RTD6T TDLY
2S43
1...100 s
1 s
Trip value PTC1
2S44
0.1...15.0 k
Ω
0.1 k
Ω
Motor Protection Relay
Technical Reference Manual - ANSI Version
REM 610
REM 610
1MRS755537
Summary of Contents for REM 610
Page 1: ...Motor Protection Relay REM 610 REM 610 Technical Reference Manual ANSI Version ...
Page 2: ......
Page 6: ...6 ...
Page 8: ...8 ...
Page 12: ...12 ...
Page 124: ...124 ...
Page 144: ...144 ...
Page 154: ...154 ...
Page 157: ......