IEC08000413.vsd
SCD file
è
do IED engineering
è
export SCD file
PCM600 (1)
è
create project
è
import SCD file
è
configure data sets
è
configure Report CBs
è
configure GOOSE CBs
è
export SCD file
CCT600 (2)
è
import SCD file
è
link GOOSE input data
è
Write to IED
PCM600 (3)
SCD file
IED 1
IED n
IED 2
IED n-1
GUID-7F3E5CB6-E662-4951-B619-D5F87B206F09 V1 EN
Figure 78:
IEC 61850: Signal engineering procedure flow when a complete
station is exported as a SCD file
7.3.1
Exporting SCL files from PCM600
A pre-condition for exporting SCL files from PCM600 is that all IEDs in the project
must be engineered in PCM600. The IEDs require unique name and IP addresses and
they must be set according to the project definitions. IED configurations must be
finalized as far as possible before starting the IEC 61850 configuration part.
7.3.1.1
Exporting SCD files
1.
Select the station in the
Plant Structure
view.
1MRS757810 C
Section 7
IEC 61850 communication engineering
REC615 and RER615
117
Engineering Manual