State
Power supply module
Ready LED
LHMI Home button
Alarm acknowledged
Process related alarm
active
Steady green
LF blinking red
No
Process related alarm
active
Steady green
Steady red
Yes
Process related alarm
has been active earlier,
but is not any more
active.
Steady green
LF blinking red
No
Process related alarm
has been active earlier,
but is not any more
active.
Steady green
Steady green
Yes
Relay set to Test Mode LF blinking green
LF blinking green
No
6.3
Correction procedures
6.3.1
Rebooting the software
1.
Select
Main menu/Configuration/General/Software reset
.
2.
Tap
Edit
, select
Activate
and tap
.
6.3.2
Restoring factory settings
In case of configuration data loss or any other file system error that prevents the
protection relay from working properly, the whole file system can be restored to the
original factory state. All default settings and configuration files stored in the factory
are restored. Only the ADMINISTRATOR can restore the factory settings.
•
Select
Configuration/General/Factory setting
to restore factory settings.
•
Tap
Edit
, select
Activate
and tap
.
The protection relay restores the factory settings and restarts.
Avoid unnecessary restoring of factory settings, because all the
parameter settings written to the relay will be overwritten with the
default values. During normal use, a sudden change of the settings can
cause a protection function to trip.
6.3.3
Setting passwords
IED Users in PCM600 is used to manage user accounts.
1MRS759118 A
Section 6
Troubleshooting
REX640
93
Operation Manual