Click
Cancel
to cancel the import. Both the WHMI and the relay
revert to the settings in use prior to the import.
GUID-D786C9E5-4FD0-4925-A0C7-8EC0E4CC4FC3 V1 EN
Figure 77:
Writing parameter settings
GUID-46164DE3-E805-4592-AA9B-6272DFD0C115 V1 EN
Figure 78:
Parameter settings written to relay
Only editable parameters are written to the relay during the
import. If part of the import fails, the faulty parameters are listed
separately.
5.20
Exporting report summary
The Report Summary page allows exporting protection relay recordings, logs and
parameters. Events, fault records and the parameter list are saved in TXT format. The
saved files contain all events, fault records and settings.
Disturbance records and load profile record files are saved in CFG and DAT formats.
1.
Select
Import/Export
on the menu bar.
2.
Select
Report Summary
from the drop-down list.
3.
Select the items to be exported.
•
Click
Select all
to select all items.
•
Click
Clear all
to clear all selections.
4.
Click
Export
to export the .zip file with the selected files.
Section 5
1MRS759118 A
Using Web HMI
80
REX640
Operation Manual