the relay over FTP/FTPS. Authentication on the LHMI is required to use USB
communication with PCM600.
If the PCM600 authentication has been enabled in PCM600 System
Settings, a relay user can be linked to the current PCM600 user by
selecting the Remember me check box in the Login dialog. After
that, the user credentials are no longer asked at tool communication
as logging in PCM600 also provides the authentication credentials
to the protection relay.
The Administrator user shall not be allowed to delete the last
ADMINISTRATOR user and itself. FTP/FTPS logins are done by
entering the username and password; there is no role selection
required. The highest role for the username is automatically
selected by the protection relay. Performing the Restore Factory
settings operation in IED Users in PCM600 restores user accounts
to the factory user accounts.
4.2
Password policies
Passwords are settable for the user accounts in all roles. Only the following
characters are accepted.
•
Numbers 0-9
•
Letters a-z, A-Z
•
Space
•
Special characters !"#%&()*+'-./:;<=>?@[]^_`{|}~
There are default password policies in the protection relay.
•
Minimum password length: 4
•
Maximum password length: 8
•
Minimum uppercase characters: 0
•
Minimum numeric: 0
•
Minimum special characters: 0
The protection relays are delivered from the factory with default passwords. It is
required to change the default passwords.
2NGA000818 A
Section 4
User management
REX610
17
Cyber Security Deployment Guideline
Summary of Contents for Relion REX610
Page 1: ...RELION PROTECTION AND CONTROL REX610 Cyber Security Deployment Guideline...
Page 2: ......
Page 8: ...Section 8 Glossary 27 Table of contents 2 REX610 Cyber Security Deployment Guideline...
Page 12: ...6...
Page 14: ...8...
Page 20: ...14...
Page 30: ...24...
Page 34: ...28...
Page 35: ...29...