background image

QU I CK STA RT G U I DE

  

Relion® REX610

 3

The most common function blocks are listed below, please refer to the 620 series Technical Manual for the full list. The 
available function blocks varies depending on the selected IED and configuration used.

Most common function blocks

Function description

IEC 61850 
identification

IEC 60617 
identification

ANSI/IEEE C37.2 
device number

Protection

Three-phase non-directional overcurrent protection, low stage

PHLPTOC

3I>

51P-1

Three-phase non-directional overcurrent protection, high stage

PHHPTOC

3I>>

51P-2

Three-phase non-directional overcurrent protection, instantaneous stage

PHIPTOC

3I>>>

50P

Three-phase directional overcurrent protection, low stage

DPHLPDOC

3I> ->

67P/51P-1

Three-phase directional overcurrent protection, high stage

DPHHPDOC

3I>> ->

67P/51P-2

Three-phase thermal protection for feeders, cables and distribution transformers

T1PTTR

3Ith>F

49F

Loss of phase, undercurrent

PHPTUC

3I<

37

Non-directional earth-fault protection, low stage

EFLPTOC

Io>

51G/51N-1

Non-directional earth-fault protection, high stage

EFHPTOC

Io>>

51G/51N-2

Non-directional earth-fault protection, instantaneous stage

EFIPTOC

Io>>>

50G/50N

Directional earth-fault protection, low stage

DEFLPDEF

Io> ->

67G/N-1
51G/N-1

Directional earth-fault protection, high stage
 

DEFHPDEF

Io>> ->

67G/N-1
51G/N-2

Negative-sequence overcurrent protection

NSPTOC

I2>M

46M

Phase discontinuity / Single phasing protection for motor

PDNSPTOC

I2/I1>

46PD

Three-phase overvoltage protection

PHPTOV

3U>

59

Three-phase undervoltage protection

PHPTUV

3U<

27

Residual overvoltage protection

ROVPTOV

Uo>

59G/59N

Multipurpose protection

MAPGAPC

MAP

MAP

Three-phase inrush detector

INRPHAR

3I2f>

68HB

Circuit breaker failure protection

CCBRBRF

3I>/Io>BF

50BF

Master trip

TRPPTRC

Master Trip

94/86

Supervision

Trip circuit supervision

TCSSCBR

TCS

TCM

Current circuit supervision

CCSPVC

MCS 3I

CCM

Fuse failure supervision

SEQSPVC

FUSEF

VCM, 60

Condition monitoring

Circuit-breaker condition monitoring

SSCBR

CBCM

52CM

Measurement

Three-phase current measurement

CMMXU

3I

IA, IB, IC

Three-phase voltage measurement

VMMXU

3U

VA, VB, VC

Residual current measurement

RESCMMXU

Io

IG

Residual voltage measurement

RESVMMXU

Uo

VG/VN

Sequence current measurement

CSMSQI

I1, I2, I0

I1, I2, I0

Disturbance recorder (common functionality)

RDRE

DR

DFR

Control

Circuit-breaker control

CBXCBR

I <-> O CB

52

Disconnector position indication

DCSXSWI

I <-> O DC

29DS

Earthing switch position indication

ESSXSWI

I <-> O ES

29GS

Autoreclosing

DARREC

O -> I

79