Single
command
function
SINGLECMD
CMDOUTy
OUTy
Function n
en04000207.vsd
Function n
IEC04000207 V2 EN-US
Figure 380:
Application example showing a logic diagram for control of built-in
functions
Single
command
function
SINGLESMD
CMDOUTy
OUTy
Device 1
User-
defined
conditions
Configuration logic circuits
en04000208_ansi.vsd
AND
ANSI04000208 V2 EN-US
Figure 381:
Application example showing a logic diagram for control of external
devices via configuration logic circuits
15.10.3
Setting guidelines
M12448-3 v2
The parameters for Single command, 16 signals (SINGLECMD) are set via the local
HMI or PCM600.
1MRK 504 163-UUS A
Section 15
Control
Transformer protection RET670 2.2 ANSI
809
Application manual