Table 65. Indications
Function
Value
Buffer capacity
Maximum number of indications presented
for single disturbance
96
Maximum number of recorded disturbances
100
Table 66. Event recorder
Function
Value
Buffer capacity
Maximum number of events in disturbance report 150
Maximum number of disturbance reports
100
Resolution
1 ms
Accuracy
Depending on
time
synchronizing
Table 67. Trip value recorder
Function
Value
Buffer capacity
Maximum number of analog inputs
30
Maximum number of disturbance reports
100
Table 68. Disturbance recorder
Function
Value
Buffer capacity
Maximum number of analog inputs
40
Maximum number of binary inputs
96
Maximum number of disturbance reports 100
Maximum total recording time (3.4 s recording time and
maximum number of channels, typical value)
340 seconds (100 recordings)
at 50 Hz
280 seconds (80 recordings) at
60 Hz
Metering
Table 69. Pulse counter PCGGIO
Function
Setting range
Accuracy
Input frequency
See Binary Input Module (BIM)
-
Cycle time for report of
counter value
(1–3600) s
-
Transformer protection RET670
1MRK 504 091-BEN B
Pre-configured
Product version: 1.1
Issued: June 2010
78
ABB