Table 12. SOM - Static Output Module (reference standard: IEC 61810-2): Static binary
outputs
Function of quantity
Static binary output trip
Rated voltage
48 - 60 VDC
110 - 250 VDC
Number of outputs
6
6
Impedance open state
~300 kΩ
~810 kΩ
Test voltage across open
contact, 1 min
No galvanic separation
No galvanic separation
Current carrying capacity:
Continuous
5A
5A
1.0s
10A
10A
Making capacity at capacitive
load with the maximum
capacitance of 0.2 μF :
0.2s
30A
30A
1.0s
10A
10A
Breaking capacity for DC with L/
R ≤ 40ms
48V / 1A
110V / 0.4A
60V / 0,75A
125V / 0.35A
220V / 0.2A
250V / 0.15A
Operating time
<1ms
<1ms
Transformer protection RET670
1MRK 504 091-BEN B
Pre-configured
Product version: 1.1
Issued: June 2010
46
ABB