HarmRestr1
: This is used to block the operation of step1 from the 2
nd
harmonic
restrain function. This function should be used when there is a risk of an unwanted
trip caused by power transformer inrush currents. It can be set to
Off
/
On
.
DirMode1
: This is used to set the directional mode of step 1. The possible modes
are
Non-directional
/
Forward
/
Reverse
.
ActLowVolt1
: This is used to define directional step behavior when the measured
voltage is below set
LowVolt
level. The possible modes of operation are
Non-
directional
/
block
/
Memory
. It is set to
Memory
by default.
8.2.3.2
Settings for step 2
GUID-3ADA3BA6-FC4B-4DD0-A545-CB48F1294B25 v1
Operation2
: This is used to
Off
/
On
the operation of step 2.
StartCurr2
: This is used to set operate phase current level for step 2 given in % of
IBase
.
tDef2
: Definite time delay for step 2. Note that the value set is the time between
activation of the start and the trip outputs.
HarmRestrain2
: This is used to block the operation of step 2 from the 2
nd
harmonic
restrain function. This function should be used when there is a risk if power
transformer inrush currents might cause unwanted trip. It can be set
Off
/
On
.
DirMode2
: This is used to set the directional mode of step 2. The possible modes
are
Non-directional
/
Forward
/
Reverse
.
ActLowVolt2
: This is used to define directional step behavior when the measured
voltage is below set
LowVolt
level. The possible modes of operation are
Non-
directional
/
block
/
Memory
. It is set to
Memory
by default.
8.3
Instantaneous residual overcurrent protection
EFRWPIOC
GUID-9131D7D1-2F18-4387-8208-07CA9DEB20CC v1
8.3.1
Identification
M14887-1 v4
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Instantaneous residual overcurrent
protection
EFRWPIOC
IN>>
IEF V1 EN-US
50N
Section 8
1MRK 506 375-UEN A
Current protection
166
Railway application RER670 2.2 IEC
Application manual
Summary of Contents for RELION RER670
Page 1: ...RELION 670 SERIES Railway application RER670 Version 2 2 IEC Application manual ...
Page 2: ......
Page 22: ...16 ...
Page 48: ...42 ...
Page 70: ...64 ...
Page 80: ...74 ...
Page 100: ...94 ...
Page 210: ...204 ...
Page 364: ...358 ...
Page 384: ...378 ...
Page 468: ...462 ...
Page 494: ...488 ...
Page 504: ...498 ...
Page 505: ...499 ...