10.4.3
Function block
GUID-E27E0BC3-CB61-4E9E-9117-6AB8906F8362 V1 EN
Figure 269:
FTAQFVR function block
10.4.4
Signals
Table 320:
FTAQFVR Input signals
Name
Type
Default
Description
I3P
GROUP
SIGNAL
-
Group signal for three phase current
U3P
GROUP
SIGNAL
-
Group signal for three phase voltage
BLOCK
BOOLEAN
0
Block of function
CBCLOSE
BOOLEAN
0
Circuit breaker closed status input
CBOPEN
BOOLEAN
0
Circuit breaker open status input
LOADINIT
BOOLEAN
0
Loads the initial accumulation time to the function
HOLDACC
BOOLEAN
0
Holds the time accumulation when input is
activated
RESETACC
BOOLEAN
0
Resetting the accumulated time of the function
block
Table 321:
FTAQFVR Output signals
Name
Type
Description
ERROR
BOOLEAN
Error output for incorrect settings
TRIP
BOOLEAN
Trip signal of the function
TRIPACC
BOOLEAN
Trip signal when accumulation time is exceeded
the set limit
TRIPCONT
BOOLEAN
Trip signal when continuous time is exceeded the
set limit
START
BOOLEAN
Start signal of the function
ACCALARM
BOOLEAN
Alarm signal for reaching the frequency time
accumulation value
Table continues on next page
Section 10
1MRK502052-UEN B
Frequency protection
558
Technical manual
Summary of Contents for Relion REG670
Page 1: ...Relion 670 series Generator protection REG670 2 0 IEC Technical manual ...
Page 2: ......
Page 44: ...38 ...
Page 58: ...52 ...
Page 80: ...74 ...
Page 106: ...100 ...
Page 482: ...476 ...
Page 548: ...542 ...
Page 570: ...564 ...
Page 600: ...594 ...
Page 608: ...602 ...
Page 630: ...624 ...
Page 862: ...856 ...
Page 1094: ...1088 ...
Page 1226: ...1220 ...
Page 1250: ...1244 ...
Page 1297: ...1291 ...