•
OEXPVPH can be connected to any power transformer side, independent from
the power flow.
•
The side with a possible load tap changer must not be used.
9.4.7.2
Operate time of the overexcitation protection
The operate time of OEXPVPH is a function of the relative overexcitation.
Basically there are two different delay laws available to choose between:
•
the so called IEEE law, and
•
a tailor-made law.
The so called IEEE law approximates a square law and has been chosen based on
analysis of the various transformers’ overexcitation capability characteristics. They
can match the transformer core capability well.
The square law is according to equation
op
2
2
0.18
0.18
t
M
1
V Hz>
k
k
overexcitation
×
×
=
-
=
æ
ö
ç
÷
è
ø
IECEQUATION2298 V2 EN
(Equation 127)
where:
M
the relative excitation
V/Hz> is maximum continuously allowed voltage at no load, and rated frequency, in pu and
k
is time multiplier for inverse time functions, see figure
.
Parameter k (“time multiplier setting”) selects one delay curve from the family of curves.
The relative excitation M is calculated using equation
measured
measured
rated
measured
measured
rated
M
U
U
f
f
UBase
UBase f
f
=
=
×
æ
ö
ç
÷
è
ø
æ
ö
ç
÷
è
ø
IECEQUATION2404 V1 EN
(Equation 128)
An analog overexcitation relay would have to evaluate the following integral
expression, which means to look for the instant of time t = t
op
according to
Section 9
1MRK502052-UEN B
Voltage protection
522
Technical manual
Summary of Contents for Relion REG670
Page 1: ...Relion 670 series Generator protection REG670 2 0 IEC Technical manual ...
Page 2: ......
Page 44: ...38 ...
Page 58: ...52 ...
Page 80: ...74 ...
Page 106: ...100 ...
Page 482: ...476 ...
Page 548: ...542 ...
Page 570: ...564 ...
Page 600: ...594 ...
Page 608: ...602 ...
Page 630: ...624 ...
Page 862: ...856 ...
Page 1094: ...1088 ...
Page 1226: ...1220 ...
Page 1250: ...1244 ...
Page 1297: ...1291 ...