7.6.8
Technical data
Table 113:
OOSPPAM technical data
Function
Range or value
Accuracy
Impedance reach
(0.00 - 1000.00)% of Zbase
±2.0% of U
r
/(√3 ⋅ I
r
)
Rotor start angle
(90.0 - 130.0) degrees
±5.0 degrees
Rotor trip angle
(15.0 - 90.0) degrees
±5.0 degrees
Zone 1 and Zone 2 trip counters
(1 - 20)
-
7.7
Loss of excitation LEXPDIS
7.7.1
Identification
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Loss of excitation
LEXPDIS
<
SYMBOL-MM V1 EN
40
7.7.2
Functionality
There are limits for the under-excited operation of a synchronous machine. A
reduction of the excitation current weakens the coupling between the rotor and the
stator. The machine may lose the synchronism and start to operate like an induction
machine. Then, the reactive power consumption will increase. Even if the machine
does not loose synchronism it may not be acceptable to operate in this state for a long
time. Reduction of excitation increases the generation of heat in the end region of the
synchronous machine. The local heating may damage the insulation of the stator
winding and the iron core.
To prevent damages to the generator it should be tripped when excitation is lost.
Section 7
1MRK502052-UEN B
Impedance protection
272
Technical manual
Summary of Contents for Relion REG670
Page 1: ...Relion 670 series Generator protection REG670 2 0 IEC Technical manual ...
Page 2: ......
Page 44: ...38 ...
Page 58: ...52 ...
Page 80: ...74 ...
Page 106: ...100 ...
Page 482: ...476 ...
Page 548: ...542 ...
Page 570: ...564 ...
Page 600: ...594 ...
Page 608: ...602 ...
Page 630: ...624 ...
Page 862: ...856 ...
Page 1094: ...1088 ...
Page 1226: ...1220 ...
Page 1250: ...1244 ...
Page 1297: ...1291 ...