Section 5
Protection-related functions
5.1
Three-phase inrush detector INR
5.1.1
Identification
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Three-phase inrush detector
INRPHAR
3I2f>
INR
5.1.2
Function block
A070377-ANSI V1 EN
Figure 151:
Function block
5.1.3
Functionality
The three-phase inrush detector function INR is used to coordinate transformer inrush
situations in distribution networks.
Transformer inrush detection is based on the following principle: the output signal
BLK2H
is activated once the numerically derived ratio of second harmonic current I_2H and the
fundamental frequency current I_1H exceeds the set value.
The trip time characteristic for the function is of definite time (DT) type.
The function contains a blocking functionality. Blocking deactivates all outputs and resets
timers.
1MRS240050-IB C
Section 5
Protection-related functions
REF615R
313
Technical Manual