Time multiplier
= 5,
Maximum trip time
= 3600000 milliseconds and
Constant delay
= 800
milliseconds.
GUID-78B05F4B-3434-4DD5-89F6-17F099444C04 V1 EN
Figure 124:
Tripping curve of “OvExt IDMT Crv4” based on the specified settings. The
two dots marked on the curve are referred to in the text.
If the excitation level stays at 1.25, the tripping occurs after 15200 milliseconds. At the
excitation level of 1.42, the time to tripping would be 5900 milliseconds as per the two
dots in
Maximum trip time
= 3600000 milliseconds
does not limit the maximum trip time because the trip time at
Pickup value
= 110% (1.1
pu) is approximately 75000 milliseconds.