Table 166:
37 Output signals
Name
Type
Description
TRIP
BOOLEAN
Trip
TRIP_A
BOOLEAN
Trip phase A
TRIP_B
BOOLEAN
Trip phase B
TRIP_C
BOOLEAN
Trip phase C
PICKUP
BOOLEAN
Pickup
PICKUP_A
BOOLEAN
Pickup phase A
PICKUP_B
BOOLEAN
Pickup phase B
PICKUP_C
BOOLEAN
Pickup phase C
4.1.9.7
Settings
Table 167:
37 Group settings
Parameter
Values (Range)
Unit
Step
Default
Description
Current block value
0.00...0.50
xIn
0.01
0.10
Low current setting to block internally
Pickup value
0.01...1.00
xIn
0.01
0.50
Current setting to pickup
Trip delay time
50...200000
ms
10
2000
Trip delay time
Table 168:
37 Non group settings
Parameter
Values (Range)
Unit
Step
Default
Description
Operation
1=enable
5=disable
1=enable
Operation Disable / Enable
Operation mode
1=Three Phase
2=Single Phase
1=Three Phase
Number of phases needed to pickup
Reset delay time
0...60000
ms
1
20
Reset delay time
4.1.9.8
Monitored data
Table 169:
37 Monitored data
Name
Type
Values (Range)
Unit
Description
PICKUP_DUR
FLOAT32
0.00...100.00
%
Ratio of pickup time / trip time
37
Enum
1=Enabled
2=blocked
3=test
4=test/blocked
5=Disabled
Status
1MRS240050-IB C
Section 4
Protection functions
REF615R
221
Technical Manual
Summary of Contents for RELION REF615R
Page 1: ... RELION PROTECTION AND CONTROL REF615R Technical Manual ...
Page 2: ......
Page 27: ...Section 18 Glossary 653 Table of contents REF615R 21 Technical Manual ...
Page 28: ...22 ...
Page 36: ...30 ...
Page 46: ...40 ...
Page 115: ...3 15 4 Settings 1MRS240050 IB C Section 3 Basic functions REF615R 109 Technical Manual ...
Page 118: ...112 ...
Page 318: ...312 ...
Page 388: ...382 ...
Page 456: ...450 ...
Page 520: ...514 ...
Page 652: ...646 ...
Page 656: ...650 ...
Page 658: ...652 ...
Page 663: ...657 ...