4.1.3.10
Monitored data
Table 110:
67/51P Monitored data
Name
Type
Values (Range)
Unit
Description
PICKUP_DUR
FLOAT32
0.00...100.00
%
Ratio of pickup time / trip time
FAULT_DIR
Enum
0=unknown
1=forward
2=backward
3=both
Detected fault direction
DIRECTION
Enum
0=unknown
1=forward
2=backward
3=both
Direction information
DIR_A
Enum
0=unknown
1=forward
2=backward
3=both
Direction phase A
DIR_B
Enum
0=unknown
1=forward
2=backward
3=both
Direction phase B
DIR_C
Enum
0=unknown
1=forward
2=backward
3=both
Direction phase C
ANGLE_A
FLOAT32
-180.00...180.00
deg
Calculated angle difference,
Phase A
ANGLE_B
FLOAT32
-180.00...180.00
deg
Calculated angle difference,
Phase B
ANGLE_C
FLOAT32
-180.00...180.00
deg
Calculated angle difference,
Phase C
67/51P
Enum
1=Enabled
2=blocked
3=test
4=test/blocked
5=Disabled
Status
Table 111:
67/50P Monitored data
Name
Type
Values (Range)
Unit
Description
PICKUP_DUR
FLOAT32
0.00...100.00
%
Ratio of pickup time / trip time
FAULT_DIR
Enum
0=unknown
1=forward
2=backward
3=both
Detected fault direction
DIRECTION
Enum
0=unknown
1=forward
2=backward
3=both
Direction information
Table continues on next page
1MRS240050-IB C
Section 4
Protection functions
REF615R
159
Technical Manual
Summary of Contents for RELION REF615R
Page 1: ... RELION PROTECTION AND CONTROL REF615R Technical Manual ...
Page 2: ......
Page 27: ...Section 18 Glossary 653 Table of contents REF615R 21 Technical Manual ...
Page 28: ...22 ...
Page 36: ...30 ...
Page 46: ...40 ...
Page 115: ...3 15 4 Settings 1MRS240050 IB C Section 3 Basic functions REF615R 109 Technical Manual ...
Page 118: ...112 ...
Page 318: ...312 ...
Page 388: ...382 ...
Page 456: ...450 ...
Page 520: ...514 ...
Page 652: ...646 ...
Page 656: ...650 ...
Page 658: ...652 ...
Page 663: ...657 ...