1MRS240173-IB B
Section 5
4x Registers
REF615R
41
DPU2000R Modbus Point List Mitigation Manual
5.1.8
Physical and Logical Input / Output state Block
REF615R maps the 4x registers with packed bits in the same address locations as in
DPU2000R. The table 17 gives an example of packed bits in 40897.
Table 17:
Mitigation of Modbus physical and logical input/output state block
40772
Sum of fault current B
1
Read addr. 42012 for
reference.
40773
sum of fault current C
1
Read addr. 42014 for
reference.
40774
Over current trip counter
1
example or explanation
40775
breaker operations counter
1
40775
1
LD0.SSCBR1.OpCnt.stVal
40776
Recloser Counter 1
1
40776
1
LD0.DARREC1.FrqOpCnt.stVal
40777
Recloser Counter 2
1
40777
1
N/A in REF615R
40778
State 1 Reclose Counter
1
40778
1
LD0.DARREC1.OpCnt1.stVal
40779
State 2 Reclose Counter
1
40779
1
LD0.DARREC1.OpCnt2.stVal
40780
State 3 Reclose Counter
1
40780
1
LD0.DARREC1.OpCnt3.stVal
40781
State 4 Reclose Counter
1
40781
1
LD0.DARREC1.OpCnt4.stVal
40782
State 5 Reclose Counter
1
40782
1
LD0.DARREC1.OpCnt5.stVal
40771
Sum of fault current A
1
42010
100
LD0.SSCBR1.AccAPwrPhA.mag.f
Can be used for Sum of fault
current A
40772
Sum of fault current B
1
42012
100
LD0.SSCBR1.AccAPwrPhB.mag.f
Can be used for Sum of fault
current B
40773
Sum of fault current C
1
42014
100
LD0.SSCBR1.AccAPwrPhC.mag.f
Can be used for Sum of fault
current C
DPU2000R
register
addr.
DPU2000R description
Scale
REF615R
register
addr.
Scale
IEC61850 path
Comments on REF615R
Modbus points mapping
DPU2000R
register
addr.
DPU 2000R description
REF615R
register
addr.
IEC 61850 path
Comments on REF615R Modbus points mapping
40897:15
Breaker is Tripping (TRIP )
40897:15
LD0.TRPPTRC1.Tr.general
40897:14
Breaker is Closing (Close )
40897:14
LD0.MVGAPC8.Q3.stVal
Configured by PCM600 tool.
40897:13
DPU is in ALARM (ALARM)
40897:13
LD0.LLN0.Health.stVal
Converted enum value to boolean to read
ALARM status
40897:12
Under voltage Trip
(27-1P )
40897:12
LD0.PHPTUV1.Op.general
40897:11
Negative Sequence
Over-current Trip (46)
40897:11
LD0.NSPTOC1.Op.general
40897:10
Phase Instantaneous
Over-current Trip (50P1)
40897:10
LD0.PHHPTOC1.Op.general
40897:9
Neutral Instantaneous
Over-current Trip (50N1 )
40897:9
LD0.EFHPTOC3.Op.general
40897:8
Phase Instantaneous
Over-current Trip (50P2)
40897:8
LD0.PHHPTOC2.Op.general
40897:7
Neutral Instantaneous
Over-current Trip (50N2 )
40897:7
LD0.EFHPTOC4.Op.general
Summary of Contents for RELION REF615R
Page 1: ...B Relion Protection and Control REF615R DPU2000R Modbus Point List Mitigation Manual...
Page 2: ......
Page 12: ...Section 1MRS240173 IB B 6 REF615R DPU2000R Modbus Point List Mitigation Manual...
Page 56: ...Section 5 1MRS240173 IB B 4x Registers 50 REF615R DPU2000R Modbus Point List Mitigation Manual...
Page 58: ...Section 6 1MRS240173 IB B 6x Registers 52 REF615R DPU2000R Modbus Point List Mitigation Manual...
Page 65: ......