132kV Busbar
200/5
33kV Busbar
500/5
P
Q
31.5 MVA
ANSI09000040-1-en.vsd
33kV 120V
/
3 3
V
AB
IED
ANSI09000040 V1 EN-US
Figure 208:
Single line diagram for transformer application
In order to measure the active and reactive power as indicated in figure
, it is
necessary to do the following:
1. Set correctly all CT and VT and phase angle reference channel
PhaseAngleRef
“Setting of the phase reference channel”
analog input channels
2. Connect, in PCM600, measurement function to LV side CT & VT inputs
3. Set the setting parameters for relevant Measurement function as shown in the
following table
:
1MRK 511 401-UUS A
Section 17
Monitoring
Bay control REC670 2.2 ANSI
519
Application manual