V2PU
is the maximal negative sequence voltage during normal operation conditions, plus a margin of
10...20%
VBase is the base voltage for the function according to the setting GlobalBaseSel
The setting of the current limit
3I2PU
is in percentage of parameter
IBase
. The setting
of
3I2PU
must be higher than the normal unbalance current that might exist in the
system and can be calculated according to equation
100
2
2
3
IBase
I
PU
I
EQUATION1758-ANSI V4 EN-US
(Equation 109)
where:
I2
is the maximal negative sequence current during normal operating conditions, plus a margin of
10...20%
IBase
is the base current for the function according to the setting
GlobalBaseSel
13.2.3.4
Zero sequence based
M13683-43 v8
The IED setting value
3V0PU
is given in percentage of the base voltage
VBase
. The
setting of
3V0PU
should not be set lower than the value that is calculated according to
.
100
3
0
3
0
3
VBase
V
PU
V
EQUATION1759-ANSI V4 EN-US
(Equation 110)
where:
3V0
is the maximal zero sequence voltage during normal operation conditions, plus a margin of
10...20%
VBase is the base voltage for the function according to the setting
GlobalBaseSel
The setting of the current limit
3I0PU
is done in percentage of
IBase
. The setting of
pickup must be higher than the normal unbalance current that might exist in the
system. The setting can be calculated according to equation
1MRK 511 401-UUS A
Section 13
Secondary system supervision
Bay control REC670 2.2 ANSI
297
Application manual
Summary of Contents for Relion REC670
Page 1: ...RELION 670 SERIES Bay control REC670 Version 2 2 ANSI Application manual ...
Page 2: ......
Page 26: ...20 ...
Page 42: ...36 ...
Page 96: ...90 ...
Page 274: ...268 ...
Page 292: ...286 ...
Page 298: ...292 ...
Page 308: ...302 ...
Page 470: ...464 ...
Page 514: ...508 ...
Page 608: ...602 ...
Page 646: ...640 ...
Page 656: ...650 ...
Page 657: ...651 ...