IEC140000127-2-en.vsd
IEC140000127 V2 EN-US
Figure 41:
An example of correct connection of SMAI and PHASORREPORT
blocks in ACT
Figure
shows an example of wrong connection of SMAI and PHASORREPORT
blocks in ACT where the same SMAI block is connected to different
PHASORREPORT blocks with different instance numbers. Such connection will be
only correct if both connected PHASORREPORT blocks have similar settings for
SvcClass and ReportRate. If settings for PMUREPORT instances differ for SvcClass or
ReportRate, then PHASOR1 connection in PHASORREPORT1 instance 2 will not be
compliant with IEEE C37.118 standard. The reason is that the filtering in SMAI/
3PHSUM block is adapted according to the performance class (SvcClass) and
reporting rate of the connected instance of PHASORREPORT function block. In this
example, SMAI1 will adapt its filtering according to PHASORREPORT instance 1
(because of higher priority) and therefore PHASORREPORT instance 2 will receive
data which does not match its performance class and report rate.
1MRK 511 401-UUS A
Section 6
Wide area measurement system
Bay control REC670 2.2 ANSI
117
Application manual
Summary of Contents for Relion REC670
Page 1: ...RELION 670 SERIES Bay control REC670 Version 2 2 ANSI Application manual ...
Page 2: ......
Page 26: ...20 ...
Page 42: ...36 ...
Page 96: ...90 ...
Page 274: ...268 ...
Page 292: ...286 ...
Page 298: ...292 ...
Page 308: ...302 ...
Page 470: ...464 ...
Page 514: ...508 ...
Page 608: ...602 ...
Page 646: ...640 ...
Page 656: ...650 ...
Page 657: ...651 ...