The PHASORREPORT filtering window is designed to receive updated input every 0.9
ms and therefore the application will fail.
Rule 2:
The same SMAI or 3PHSUM block can be connected to more than one
PHASORREPORT block only if all the connected PHASORREPORT blocks have
similar instance number or only if all the connected PHASORREPORT blocks have
similar settings for SvcClass and ReportRate. Figure
PMUREPORT function block demonstrated by PCM600 Parameter Setting Tool
(PST).
IEC140000126-2-en.vsd
IEC140000126 V2 EN-US
Figure 40:
PMUREPORT settings in PCM600 PST
shows an example of correct connection of SMAI and PHASORREPORT
blocks in ACT where two different SMAI blocks are connected to different
PHASORREPORT blocks with different instance numbers. In this example, as the
PHASORREPORT blocks have different instance numbers and different settings for
SvcClass and ReportRate, a separate SMAI block is used for each PHASORREPORT
block.
Section 6
1MRK 511 401-UUS A
Wide area measurement system
116
Bay control REC670 2.2 ANSI
Application manual
Summary of Contents for Relion REC670
Page 1: ...RELION 670 SERIES Bay control REC670 Version 2 2 ANSI Application manual ...
Page 2: ......
Page 26: ...20 ...
Page 42: ...36 ...
Page 96: ...90 ...
Page 274: ...268 ...
Page 292: ...286 ...
Page 298: ...292 ...
Page 308: ...302 ...
Page 470: ...464 ...
Page 514: ...508 ...
Page 608: ...602 ...
Page 646: ...640 ...
Page 656: ...650 ...
Page 657: ...651 ...